An N2-BLAST replaces the compressed air in a dry or pre-action sprinkler system with high-purity nitrogen. Oxygen is what drives corrosion inside sprinkler piping; take the oxygen out and oxygen-driven corrosion largely stops. The generator makes its own nitrogen on site from compressed air, holds it in storage, and feeds the system through the air maintenance device the same way a compressor would. Filling the system is only half the job — the air already trapped in the piping has to be purged out, which is what the AutoPurge Systems below are for.
This article is the starting point. Find your model family below, then work from that family's articles — the models differ enough that guidance written for one will mislead you on another.
Start by identifying the unit
Read the model number off the nameplate on the unit before you open any article or manual. Do not go by the size of the cabinet, by what is on the purchase order, or by what the last technician wrote on the service tag. Cabinets were reused across models and across the legacy and current lines.
Current model families
| Family | Form | Where to start |
|---|---|---|
|
FPS-500, FPS-900 and FPS-900-RS |
Compact, wall mounted. Optional air compressor. | FPS-500 and FPS-900 Overview |
| FPS-1650, FPS-3250, FPS-5000 | Mid-range cabinet with an internal nitrogen storage tank. Compressor options from 2 to 10 HP. | FPS-1650, FPS-3250, and FPS-5000 Overview |
| FPS-10000, FPS-16500, FPS-22500 | Large cabinet. Air dryer is internal, plumbed and piped inside the generator. | FPS-10000, FPS-16500, and FPS-22500 Overview |
Legacy model families
These units are no longer built. They are still in service and still supported, but they are documented separately and the current-line specifications do not apply to them.
| Family | Where to start |
|---|---|
| FPS-650, FPS-1250 | FPS-650 and FPS-1250 Legacy Overview |
| FPS-1750, FPS-3000, FPS-6000 | FPS-1750, FPS-3000, and FPS-6000 Legacy Overview |
| FPS-15000, FPS-20000 | FPS-15000 and FPS-20000 Legacy Overview |
| All legacy models | Legacy N2-BLAST Fire Protection Systems Overview |
What every current N2-BLAST delivers
| Specification | Value | What it means for you |
|---|---|---|
| Nitrogen purity | 98.5% or better | A minimum, measured at the generator outlet. It is not a statement about what any one sprinkler zone is reading — a zone reaches its own purity over time as the trapped air is purged out, and is judged against the setpoint programmed for that zone. |
| Product gas dew point | -35 °F | Far drier than compressed air, and the reason nitrogen carries almost no moisture into the piping. It depends on the feed air meeting specification, which matters most where the compressor and dryer are supplied by others. |
| Nitrogen source | Generated on site | Pressure swing adsorption, from ordinary compressed air. No cylinder deliveries, no dewar, no bulk contract. |
Why nitrogen instead of air
Oxygen-driven corrosion inside sprinkler piping needs three things: steel, water and oxygen. The steel is the system. The water is managed by pitch, low point drains and draining the system properly after every trip — and nitrogen does not change any of that. What nitrogen removes is the third one: the oxygen.
Compressed air is roughly 21% oxygen, and a dry or pre-action system holds that air against wetted pipe walls for years at a time. Nitrogen at 98.5% or better leaves no more than 1.5% of anything else, and only part of that is oxygen. In long-term corrosion testing of Schedule 10 coupons held half full of water, nitrogen supervision extended projected service life substantially over compressed air:
| Schedule 10 pipe | Projected on compressed air | Projected on nitrogen |
|---|---|---|
| Black steel | 20 years | 63 years |
| Galvanized steel | 10 years | 176 years |
Nitrogen is also far drier than compressed air. At a -35 °F dew point there is very little water vapor in the supervisory gas to condense inside the pipe, which takes away one corrosion driver and one contributor to ice plugs in unheated spaces.
Nitrogen supervision of dry and pre-action systems is well established, but acceptance is the authority having jurisdiction's call on any given job — confirm it with them before you specify.
Why Nitrogen Is Used in Fire Protection Systems covers the mechanism in full, and Nitrogen Supervision vs. Vapor Corrosion Inhibitors (VCI) compares the two approaches.
How the generator makes nitrogen
Every N2-BLAST uses pressure swing adsorption. Compressed air is fed through a vessel packed with carbon molecular sieve. The sieve pore size is tuned so that oxygen molecules, which are slightly smaller, are held in the pores while the larger nitrogen molecules pass through. Nitrogen leaves the vessel as product gas; the oxygen is released to atmosphere when the vessel depressurizes.
Current-line units run two beds, marked A and B. One produces while the other regenerates, then they swap — which is why a running generator cycles audibly rather than holding steady, and why that cycling is normal rather than a fault.
What goes with the generator
A generator on its own fills the piping. The accessories are what get the trapped air out and tell you whether it worked. These are the current-line accessories; a legacy system may have been supplied with different equipment.
| Accessory | What it does | More |
|---|---|---|
| AutoPurge System (APS) | A calibrated purge point on each zone. Bleeds oxygen-rich trapped air out at a set rate so nitrogen can replace it. Fully pneumatic — no power needed. Where a Quick-Check manifold is fitted, purging on a zone stops once that zone is in specification. | AutoPurge and Quick-Check Overview |
| Quick-Check purity manifold | Monitors nitrogen purity from one cabinet — one zone per port — and stops purging a zone once it is in specification. Available in 1, 6, 10 and 20 port, so the port count has to match the number of zones. | AutoPurge and Quick-Check Overview |
| Quick-Check portable purity sensor | Handheld. Reads one zone at a time at the APS. | Quick-Check Accessories Overview |
| BlastOff and SMART-Trak | Leak detection, air bypass alarm, early warning and onboard purity monitoring, plus run-time tracking and remote monitoring. | BlastOff and SMART-Trak Overview |
Keeping it running
Current line. Legacy models have different filters and different intervals — work from the legacy articles above for those.
| Task | When | Where |
|---|---|---|
| Change the filters | Annually, or every 1,000 run hours — whichever comes first | Annual Filter Replacement (FRP-007) |
| Clean the strainer on each APS | Quarterly | APS Typical Installation Guide |
| Check purity in each zone | Quarterly | AutoPurge and Quick-Check Overview |
| Check run time | Quarterly. A generator running far longer than it used to usually means the system is leaking, but fouled filters, a stuck-open APS or aging sieve will do the same thing. | BlastOff and SMART-Trak Overview |
| Find and fix leaks | Whenever run time climbs or purity will not hold | System Leak Check Procedure |
If the generator stops
This is the first question most people ask, so it is worth answering plainly. Nitrogen purity is a corrosion control function, not a fire protection function. A generator that has faulted, been switched off or been isolated for service does not disable the sprinkler system, and it does not put the building out of protection.
| What keeps working | What to do about it |
|---|---|
| The sprinkler system stays a functioning dry or pre-action system. Supervisory pressure is held through the air maintenance device, and the building fire alarm supervises that pressure independently of anything the generator does or reports. | Nothing, immediately. Treat it as equipment down, not as a system impairment. |
| Where air bypass is fitted, the air compressor takes over and holds supervisory pressure while the generator is out. | Expect an air bypass alarm — that is the alarm doing its job. Restore the generator and return the system to nitrogen. See How Do I Manually Activate Bypass Mode. |
| Purity starts to drift. Every hour on air is oxygen going back into the piping. Corrosion protection degrades gradually, not instantly. | Get the generator running, then confirm every zone comes back within its setpoint. A long outage may need a fresh purge period. |
How long until the system is protected
Not on the day it is commissioned. Filling a dry system with nitrogen leaves the air that was already in the piping exactly where it was, and driving that out takes weeks. A newly commissioned system reads out of specification, and that is correct rather than a fault.
The monitoring equipment has a setting for this period — an Initial System Purge, factory default 40 days — which lets the zones purge without raising a purity alarm the whole time. How long a given zone actually takes depends on its volume and how well it was purged.
Articles by model family
FPS-500 and FPS-900
- Overview
- Site and Utility Requirements
- Installation and Startup
- Operation, Alarms, and Maintenance
- Preventative Maintenance
FPS-1650, FPS-3250, and FPS-5000
- Overview
- Site and Utility Requirements
- Installation and Startup
- Operation, Alarms, and Maintenance
- Preventative Maintenance
FPS-10000, FPS-16500, and FPS-22500
- Overview
- Site and Utility Requirements
- Installation and Startup
- Operation, Alarms, and Maintenance
- Preventative Maintenance
Across the line
- AutoPurge and Quick-Check Overview for N2-BLAST Systems
- BlastOff and SMART-Trak Overview for N2-BLAST Systems
- Fire Alarm and BMS Wiring for FPS Generator Dry Contacts
- Contractor Installation and Startup Checklist
- PLC Fatal Error: Re-initialization and Parameter Restore
Manuals
- FPS-500 Manual
- FPS-900 Manual
- FPS-1650, FPS-3250, and FPS-5000 Manual
- FPS-10000, FPS-16500, and FPS-22500 Manual