The FPS-1650, FPS-3250, and FPS-5000 are floor-standing nitrogen generators built for fire protection. They supply 98.5%+ nitrogen into dry-pipe and pre-action sprinkler systems to displace the oxygen and moisture that drive pipe corrosion. This is the mid-range of the N2-BLAST® line and the most commonly installed group — a step up from the compact FPS-500/900, and built around a touchscreen controller with full data logging, automatic air bypass, and BlastOff® leak detection where ordered.
Where these three sit in the N2-BLAST line
If you are not certain which article you need, find your model here first. All eight current models do the same job; they differ in how much piping they can supervise and where the compressed air comes from.
| Model | Largest single zone | Layout | Compressor |
|---|---|---|---|
| FPS-500 | 500 gal | Modular, wall or rack mounted | Internal |
| FPS-900 | 900 gal | Modular, wall or rack mounted | Internal |
| FPS-1650 | 1,650 gal | Integrated, floor standing | Internal, oil-free |
| FPS-3250 | 3,250 gal | Integrated, floor standing | External |
| FPS-5000 | 5,000 gal | Integrated, floor standing | External |
| FPS-10000 | 10,000 gal | Integrated twin-tower skid | External |
| FPS-16500 | 16,500 gal | Integrated twin-tower skid | External |
| FPS-22500 | 22,500 gal | Integrated twin-tower skid | External, often duplex |
What these systems do
Oxygen and moisture trapped in sprinkler piping drive electrochemical, galvanic, and microbiologically influenced corrosion (MIC) — the leading cause of premature pipe failure in dry and pre-action systems. Replacing that air with 98.5%+ nitrogen interrupts the corrosion reaction at its source. The generator holds a nitrogen supervisory atmosphere in the piping at low flow, running in the background and topping the system up as gas is consumed through small leaks and trip events. Background and the supporting corrosion data are in Why Nitrogen Is Used in Fire Protection Systems.
How the system works
Compressed air is filtered and fed to pressure swing adsorption (PSA) beds packed with carbon molecular sieve. The sieve adsorbs oxygen under pressure and lets nitrogen pass through to an internal storage tank; the controller alternates the beds so one side is producing while the other regenerates, giving continuous output. The bed count is not the same across the three models — the FPS-1650 and FPS-3250 each carry two beds, while the FPS-5000 carries four in a tetrad arrangement. All three use the same 48" bed fabrication; the FPS-1650's is drawn as 4" OD × 48", and the FPS-3250 and FPS-5000 use the same bed at a nominal 4" diameter. The FPS-3250 gets its extra capacity over the FPS-1650 from a larger-bore flow path and a larger external air supply rather than from more beds; the FPS-5000 adds two more beds on top of that. Production starts and stops automatically on storage tank pressure. The sieve is not consumed in the reaction, so with clean dry feed air it is a long-life component — which is exactly why the filtration and dew point requirements matter so much, and why water carryover into the beds is the one failure that is not recoverable. Air consumption depends on the purity and flow you are asking for, so there is no single air-to-nitrogen ratio; peak feed-air demand can reach up to three times the average, and South-Tek sizes the feed compressor for the job.
| Feature | What it does | Models |
|---|---|---|
| Filtration | Three stages on every model, replaced together once a year. On the FPS-1650: an intake pre-filter on the internal compressor, then a particulate and coalescing pair in a single combination body. On the FPS-3250 and FPS-5000: a 5-micron filter/regulator combo at the air inlet ahead of the dryer, then a 0.01-micron coalescing filter and an adsorbing filter in a separate assembly after the dryer. Every filter in the air train downstream of the compressor has an auto-drain and needs a drain line. The FPS-1650's compressor intake pre-filter and the FPS-3250/FPS-5000 adsorbing filter do not. | All three |
| Nitrogen storage | A nitrogen tank inside the cabinet with ball valves, ASME safety relief and a gauge, feeding an external manual ball valve for the site connection. Nominal capacity is 14.8 gal. | All three |
| Automatic cut-in / cut-out | A pressure transducer signals the controller to start and stop production. Setpoints are factory set — read them off the controller's N2 Pressure Settings screen and record them, and do not adjust them without consulting South-Tek. | All three |
| Touchscreen controller | A UL 508A panel with a graphical interface, live system status, sensor and performance logging, trend graphs, and remote monitoring over Ethernet or Modbus TCP/IP. Programs are proprietary and password-protected. | All three |
| Automatic air bypass | If the generator cannot keep up with demand, the system switches the riser to compressed air, alarms, and logs the time spent in bypass. It also triggers during the 30-minute fire protection piping fill test, which is a normal cause and not a fault. The bypass cut-in and cut-off values are on the controller's Bypass Settings screen — read and record them from the unit. Automatic bypass starts at the FPS-1650 — the FPS-500/900 use a manual bypass valve. | All three — see the note below on optionality |
| Safety relief | ASME safety relief valves protecting against component failure. Read the set pressure off the tag on the valve itself — never disable, plug, or adjust one. | All three |
| AutoPurge System (APS) | A patented pneumatic device, one per riser, that continuously bleeds residual air out at the remote end of the piping so the zone actually reaches and holds 98.5% nitrogen. It needs no power and stays in service continuously — a riser-room purge alone cannot reach dead-end runs. It does need to be tuned to the system at commissioning — see AutoPurge System (APS) Field Tuning Instructions. Confirm the APS quantity and scope of supply against the order. | All three |
| Monitoring outputs | Voltage-free dry contacts for a fire alarm panel or BMS — common alarm, a separate bypass alarm relay where auto air bypass is fitted, a purity contact where the oxygen sensor is fitted, and an optional power loss contact — plus analog outputs for tank pressure and tank trace O₂ — 0–10 V on the FPS-1650; on the FPS-3250 and FPS-5000 confirm the range and scaling against the drawing package supplied with the unit before specifying the receiving equipment. Receiving equipment is installed by others. The power loss contact is wired the opposite way round to the common alarm; behaviour and terminals are in Operation and Alarms. | All three |
| Air source | The FPS-1650 carries its own oil-free compressor inside the cabinet, with a pre-compressor intake filter. The FPS-3250 and FPS-5000 are fed by an external compressor and need refrigerated drying to hold the feed-air dew point below 40°F. Drying is an ordered option: it is either a dryer fitted inside the generator cabinet or a separate dryer standing in the room. On the FPS-3250 a cabinet dryer is powered from the generator's own supply; on the FPS-5000 confirm the arrangement against the drawing package supplied with the unit. Confirm which is on the job — it changes site prep, startup and maintenance. | Differs |
The BlastOff® feature set
All four BlastOff® levels are available on this group. Level II, automatic air bypass, starts at the FPS-1650 — the smaller FPS-500/900 bypass manually.
| Level | Name | What it gives you |
|---|---|---|
| I | Leak detection | Tracks generator runtime and alarms if it runs past the BlastOff® timer setting without reaching Standby, giving warning before a potential low-air alarm. The timer setting and its countdown are on the BlastOff® settings screen — it is configurable. Audible, visual, and dry-contact output to a building management system. |
| II | Automatic air bypass | Automatically switches between compressed air and nitrogen if the generator cannot keep up, alarms, and tracks and logs time spent in bypass. Available on the FPS-1650 and larger. |
| III | Early warning | Trouble alarm with diagnostics — confirms all components are working and helps pinpoint a leak location within the nitrogen system. |
| IV | Onboard purity | Monitors the nitrogen purity going into the fire protection system, trends it graphically, and alarms below the configured O₂ purity alarm point — that point is on the O₂ Purity Alarm Settings screen, and 98.5% is the system's purity specification rather than a fixed alarm point. |
Operating pressures
| Pressure | FPS-1650 | FPS-3250 & FPS-5000 |
|---|---|---|
| Cut-in and cut-out (production start and standby) | Read them off the unit. The cut-in and cut-out pressures are on the controller's N2 Pressure Settings screen. Record them on the service record before you diagnose a pressure complaint, and do not adjust them without consulting South-Tek. | |
| Automatic bypass cut-in / cut-off | Read them off the unit. The bypass cut-in and cut-off are on the controller's Bypass Settings screen. Where the bypass air supply shuts off below the cut-off, the cut-off is set 5 PSIG below that shut-off pressure and the cut-in 10 PSIG below the cut-off. Record both values before diagnosing a bypass complaint. | |
| Feed air at the generator inlet | Self-supplied — none required | The cabinet inlet regulator is factory set at 120–125 PSIG and is what the generator runs on — it is not a field adjustment. South-Tek-supplied feed compressors are preset to cut out at 175 PSIG; a compressor bought elsewhere must be confirmed with South-Tek before it is selected. Dew point below 40°F. The line pressure arriving at the cabinet is the compressor's, not the generator's, so rate the feed piping and fittings for 175 PSIG. Running the generator itself above 125 PSIG, by altering the cabinet inlet regulator, can cause damage that is not covered under warranty. |
Specifications
| Specification | FPS-1650 | FPS-3250 | FPS-5000 |
|---|---|---|---|
| Nitrogen purity | 98.5%+ | ||
| Coverage (largest single zone) | 1,650 gal | 3,250 gal | 5,000 gal |
| PSA sieve beds | Two, 4" OD × 48" | Two, 48" (nominal 4" diameter) | Four, 48" (tetrad; nominal 4" diameter) |
| Internal storage tank | 14.8 gal nominal, with ASME safety relief. The vessel rating is not published per model — read it off the tank data plate on the unit | ||
| Cabinet (W x D x H) | 26" x 18" x 59" — about 63.6" overall to the top gas fitting | ||
| Approximate weight | 223 lb | 243 lb | 303 lb |
| Electrical | 120–240 VAC, 50/60 Hz, 1-ph, < 8 A. Supply voltage is factory configured and cannot be changed after build — read the product information label on the unit to confirm what it was built for. | 120–240 VAC, 50/60 Hz, 1-ph, < 5 A for the generator alone. On the FPS-3250 a dryer fitted inside the cabinet runs off the generator's supply and is not in that figure; on the FPS-5000 confirm the arrangement against the drawing package supplied with the unit. Size the branch circuit to the unit nameplate and local code, not to the draw figure. The external compressor needs its own service | |
| Over-current protection | 15 A at the cabinet power entry module. It protects the generator — it is not the branch-circuit protection and not a disconnecting means. Size and protect the branch circuit to the unit nameplate and local code, and provide a lockable disconnecting means ahead of the cabinet | ||
| Compressor | Integral, oil-free, with an intake pre-filter. Units ordered with the backup air compressor option carry two | External, supplied and piped separately | |
| Gas connections | 1/2" NPT female unless otherwise stated | ||
| Drain connections | Two 1/4" OD, low on the left side | Two 1/4" NPT female bulkheads fitted with push-to-connect connectors, low on the left side, with the run made in 1/4" OD tubing — current builds; on units built before 2024 confirm the connector type at the port before ordering drain material | |
| Ambient temperature | 40–100°F (4–38°C) | ||
| Noise level | < 90 dBA | ||
| Installation | Floor standing, indoors, on a hard flat surface rated for the installed weight with margin — up to about 303 lb for the FPS-5000, plus the feed compressor and any receiver on the FPS-3250 and FPS-5000 | ||
| Filter kit — replace at 12 months or 1,000 run hours, whichever comes first | FRP-007 | FRP-022 (current, white ASCO filters) — legacy black-bowl units take FRP-013 | |
Approvals and certifications
| Approval | Detail |
|---|---|
| FM Approval | FM Approval is held per assembly rather than as a blanket listing on the model line, and it varies with the configuration ordered. If the job is FM-insured, obtain South-Tek's written confirmation of FM Approval status for the specific model and configuration ordered, including the standard it is listed under, and give it to the AHJ and the insurer before the equipment is set. |
| UL | The control panel is built to UL 508A as an open-type industrial control panel. That covers the control panel, not the generator as a whole, and it is an open assembly protected only by the cabinet — there is no dead front behind the left-side cover. Electrical schematics are available from South-Tek on request. |
| CE | CE marked on CE-configured units. CE is a distinct build, not a property of the model line — it has its own cabinet fabrication, its own labelling (CE serial, ground symbol, arc-flash caution) and an alternate supply voltage. Specify CE at order; it is not a retrofit. |
| Pressure relief | ASME safety relief valves are fitted throughout. Vessel and valve ratings are not published per model — read them off the tank data plate and the valve tag on the unit. |
Typical installation profile
Full requirements are in FPS-1650, FPS-3250, and FPS-5000 Site and Utility Requirements. In outline:
- Indoor, nonhazardous, well-ventilated location at 40–100°F, floor standing on a flat surface rated for the unit's weight with margin.
- The cabinet's left side is the electrical face — power entry module, UL 508A panel, touchscreen, certification and torque labels, and both drain connections. NEC 110.26 working space applies there, not at the front: 36" deep, 30" wide or the equipment width whichever is greater, and 6.5 ft high, kept clear. Allow 36" at the front for the filter change and routine maintenance, 6" minimum on the remaining sides for ventilation, and clearance above the cabinet for gas-line connections.
- Two drain lines exit low on the cabinet's left side — 1/4" OD on the FPS-1650, 1/4" NPT bulkheads with push-to-connect connectors on the FPS-3250 and FPS-5000. Plumb them individually to the nearest site drain and leave them open to atmosphere.
- The FPS-3250 and FPS-5000 need an external air compressor sized to the system, plus refrigerated drying to hold the feed-air dew point below 40°F. Drying may be fitted inside the generator cabinet or stand separately in the room — confirm which from the order documents before mobilizing, because it changes the power, the drain and the floor space you have to provide.
- Power is 120–240 VAC single phase landed at the cabinet's power entry module, which carries the generator's built-in 15 A over-current protection. That device is not the branch-circuit protection and not a disconnecting means, so provide a lockable disconnect ahead of the cabinet and an equipment grounding conductor. Hard-wired and receptacle connections are both used. An external compressor has its own service, often three-phase, and its rotation must be verified at startup.
- One air maintenance device (AMD) per riser in the downstream piping, plus bypass piping around the generator.
Identifying your unit before you follow a procedure
Confirm the exact model number on the nameplate before following a procedure or ordering parts. These three share a platform but are not interchangeable in service. The difference that matters most is the air source: the FPS-1650 supplies its own air, while the FPS-3250 and FPS-5000 depend on an external compressor and drying, which changes site preparation, the startup sequence, the alarm set, the annual filter kit, and the preventive maintenance schedule.
Related articles
- Annual Filter Replacement — FPS-500, FPS-900, FPS-900-RS, FPS-1650 (FRP-007)
- N2-BLAST Fire Protection Systems Overview
- Why Nitrogen Is Used in Fire Protection Systems
- FPS-1650, FPS-3250, and FPS-5000 Site and Utility Requirements
- FPS-1650, FPS-3250, and FPS-5000 Installation and Startup
- FPS-1650, FPS-3250, and FPS-5000 Operation and Alarms
- FPS-1650, FPS-3250, and FPS-5000 Preventive Maintenance
- N2-BLAST® FPS-1650, FPS-3250 & FPS-5000 — Safety Guidelines
- What BlastOff Means and What to Check First
- FPS-500 and FPS-900 Overview
- FPS-10000, FPS-16500, and FPS-22500 Overview