Applies to: APS2 and APS4 AutoPurge System units on South-Tek N2-BLAST fire protection nitrogen generators.
This is the lookup table. It gives the flow setting for a zone of a given volume, for each APS model. It is a reference, not a procedure — for how to actually set the dial, and for what to do when the bead will not lift or will not hold, see APS Field Tuning Instructions.
▲ Attention — with a PowerSaver manifold, ignore this table If the zone reports to a Quick-Check PowerSaver manifold, the flow setting is D — on both APS2 and APS4, at every zone size, regardless of what this table or the label on the unit gives for that volume. The manifold changes what the APS is doing, so zone volume no longer selects the setting. This supersedes the note printed on the unit's own label, which cannot be removed and does not say so. Use the tables below only where no manifold is connected.
How to read these tables
Three things decide which row you want.
- The APS model. APS2 and APS4 cover different volume ranges and do not overlap. The model is on the front of the unit.
- The volume of that zone in gallons — the zone the APS is installed on, not the whole system. Where it was never recorded, it has to be established before the APS can be set at all.
- Whether a manifold is connected. See the box above. This is the case that overrides everything else.
The settings are positions on the sight tube. The lettered marks run A at the bottom to E at the top, with graduations between them, and you read the center of the float bead against the scale — not its top or bottom edge. The difference is most of a quarter step.
ℹ Note — the label on the unit is the field reference Every APS carries these settings on a label on its back. That label is the primary reference at the device and the tables below reproduce it. If the two ever disagree, stop and call South-Tek Tech Support rather than choosing one. Do not paint over the label, cover it, or mount a unit with the label against a wall.
The label also carries two instructions worth repeating here. Set the flow once the system is at supervisory pressure. And if no flow occurs, use the bleed screw below the label to relieve the water check feature before assuming a fault — see APS Field Tuning Instructions for how, and for what to do if flow does not return.
The label also carries two instructions worth repeating here. Set the flow once the system is at supervisory pressure. And if no flow occurs, use the bleed screw below the label to relieve the water check feature before assuming a fault — see APS Field Tuning Instructions for how, and for what to do if flow does not return.
APS2 flow settings
Zones from 50 to 1,050 gallons.
| Zone (gallons) | Flow setpoint | Zone (gallons) | Flow setpoint |
|---|---|---|---|
| 50 | 1/4 | 600 | C |
| 100 | 1/2 | 650 | C+1/4 |
| 150 | 3/4 | 750 | C+1/2 |
| 200 | A | 800 | C+3/4 |
| 250 | A+1/2 | 850 | D |
| 300 | A+3/4 | 900 | D+1/4 |
| 350 | B | 950 | D+1/2 |
| 400 | B+1/4 | 1,000 | D+3/4 |
| 500 | B+1/2 | 1,050 | E |
| 550 | B+3/4 |
APS4 flow settings
Zones from 1,100 to 4,000 gallons. Note these are ranges, where the APS2 settings are single volumes.
| Zone (gallons) | Flow setpoint | Zone (gallons) | Flow setpoint |
|---|---|---|---|
| 1,100–1,200 | A | 2,600–2,750 | B+3/4 |
| 1,250–1,500 | A+1/4 | 2,800–3,050 | C |
| 1,550–1,700 | A+1/2 | 3,100–3,300 | C+1/4 |
| 1,750–1,900 | A+3/4 | 3,350–3,600 | C+1/2 |
| 1,950–2,050 | B | 3,650–3,850 | C+3/4 |
| 2,100–2,300 | B+1/4 | 3,900–4,000 | D |
| 2,350–2,550 | B+1/2 |
Zones the tables do not cover
| If the zone is | What to do |
|---|---|
| Between 1,050 and 1,100 gallons | Neither table covers it — APS2 ends at 1,050 and APS4 begins at 1,100. Call South-Tek Tech Support. Do not round to the nearest row and do not extrapolate a setting. |
| Under 50 gallons, or over 4,000 gallons | Outside the range of both models. Call Tech Support — the zone may need a different APS model or more than one purge point. |
| Not a volume in the table, but inside the APS2 range | The APS2 settings are listed as single volumes, not ranges, and no South-Tek document defines what to do with a zone that falls between two rows. Call South-Tek Tech Support with the zone volume rather than rounding to a neighboring row — the two rows either side of a gap can be a quarter to a half step apart, and a zone set to the wrong one is either short of specification or venting nitrogen continuously. |
| Between two APS4 ranges | The APS4 ranges are not continuous — there are twelve gaps between them, for example 1,225 or 2,575 gallons. As with the APS2 table, no South-Tek document defines which range to take. Call Tech Support with the zone volume. Do not round to the nearer range. |
| Of unknown volume | It cannot be set from this table. Establish the volume first — it is far easier to work out at installation than later. With a manifold connected the volume does not matter; the setting is D. |
Before you change a setting
⚠ Warning — valve the APS off during any pressure test The label on every unit carries this instruction: AutoPurge Systems should be valved off during all FPS pressure tests. This system allows a controlled purge of the FPS system and should be set to the proper APS Flow Setting only. Other settings may cause the FPS to alarm or malfunction. An APS left open during a pressure test bleeds a slow purge and distorts the result. Reopen every valve you closed before you leave site — a zone whose APS is still shut does not purge, and on a system with no manifold nothing anywhere reports it.
- Set it at supervisory pressure. A zone still coming up to pressure will not give a steady bead, and a setting made against a falling or rising pressure is not repeatable.
- Start from fully closed, then open counter-clockwise to the setting. Adjusting by feel from wherever the dial happens to sit does not give a repeatable flow. This is the tuning procedure rather than anything printed on the label — see APS Field Tuning Instructions.
- Do not open the dial past the setting to speed a zone up. A zone drives its trapped air out over an extended period. Over-purging vents nitrogen continuously and runs the generator for nothing.
- If the bead does not lift at all, there is no flow through the APS and opening the dial further fixes neither cause. Go to the troubleshooting section of APS Field Tuning Instructions.
Related articles
- AutoPurge System (APS) Field Tuning Instructions
- APS Typical Installation Guide
- Quick-Check PowerSaver Manifold — Installation and Commissioning
- AutoPurge and Quick-Check Overview for N2-BLAST Systems
- N2-BLAST Fire Protection Systems Overview
Need help? South-Tek Systems Service — Phone: (910) 415-1880 · Open a support ticket at support@southteksystems911.zendesk.com or through the Help Center.