This article provides general setup guidance for AutoPurge System (APS) installations that include Quick-Check or PowerSaver monitoring accessories on supported South-Tek N2-BLAST fire protection systems.
When these accessories are installed, the APS tuning process differs slightly from a standard APS-only installation. Proper setup is important to ensure accurate adjustment and normal operation after the manifold or monitoring connection is restored.
This article is intended as a general reference for setup and commissioning. Always verify the installed configuration and follow applicable South-Tek instructions for the specific equipment in use.
Overview
Quick-Check and PowerSaver accessories may be connected to the APS using the adapter port and 1/4" OD tubing. These accessories are used to help verify or monitor nitrogen purity within the fire protection system.
Because the connected tubing and manifold can influence the APS during adjustment, the tubing should be temporarily disconnected while the APS is being tuned.
When this guidance applies
Use this setup guidance when the APS is connected to:
- A Quick-Check purity manifold
- A PowerSaver manifold
- Other compatible monitoring accessories connected through the APS adapter port
Before you begin
Before adjusting the APS, confirm the following:
- The fire protection system is at supervisory pressure
- The APS has been installed correctly
- The APS ball valve is open for normal operation
- The Quick-Check or PowerSaver tubing is accessible at the APS adapter connection
- The correct APS model and applicable settings are being referenced
Setup procedure
- Bring the fire protection system to supervisory pressure.
- Verify that the APS ball valve is in the open position.
- Locate the 1/4" OD tubing connected to the APS adapter.
- Disconnect the tubing from the APS adapter before adjusting the APS flow.
- Turn the APS flow dial fully to the closed position.
- Adjust the APS flow dial to the applicable setting for the installed configuration.
- Allow the float bead to stabilize at the intended setting.
- Reconnect the 1/4" OD tubing after the float bead has stabilized.
What to expect after reconnecting tubing
After the tubing is reconnected, the float bead may drop slightly. This can occur due to the normal operation of the connected Quick-Check or PowerSaver manifold.
A slight change after reconnecting the tubing is typically normal as long as the APS was adjusted correctly before reconnection and the system is otherwise operating as expected.
Why the tubing is disconnected during setup
The APS should be adjusted without the connected tubing in place so the flow setting can be established correctly at the APS itself. Leaving the tubing connected during adjustment may affect the observed float position and lead to an improper setting.
Disconnecting the tubing during setup helps provide a more accurate and repeatable APS adjustment.
Final verification
After setup is complete, verify the following:
- The 1/4" OD tubing has been reconnected securely
- The APS flow setting was established before reconnecting the tubing
- The APS ball valve remains in the proper operating position
- The system is at supervisory pressure
- No loose tubing or unintended purge condition is present
Common setup mistakes to avoid
- Adjusting the APS with the tubing still connected
- Failing to start with the APS flow dial in the closed position
- Tuning the APS before the system is at supervisory pressure
- Forgetting to reconnect the tubing after adjustment
- Assuming a small float change after reconnection indicates a fault
When to contact support
Contact South-Tek Systems support if the APS does not appear to stabilize correctly, if the connected manifold does not behave as expected after reconnection, or if there is uncertainty about the proper APS model or target setting for the installed configuration.
Related articles
- AutoPurge and Quick-Check Overview for N2-BLAST Systems
- AutoPurge System (APS) Typical Installation Guide
- AutoPurge System (APS) Field Tuning Instructions
- N2-BLAST Fire Protection Systems Overview
Need additional support?
- Phone: (910) 415-1880
- Email: support@southteksystems911.zendesk.com