Tuning sets how fast one zone purges. Get it right and the zone reaches its purity setpoint and holds it; get it wrong and the zone either never comes into specification or vents nitrogen continuously and runs the generator and compressor for nothing.
Every APS is tuned individually, and one APS serves one zone. Tune each one against that zone's own volume.
This article covers tuning only. For where the APS goes and how it is piped, see APS Typical Installation Guide.
Before you start
Have all four of these before you touch the dial:
- The system is at supervisory pressure. There is no flow to set below it, and a bead set on a partly pressurized system will not hold its setting.
- Installation is complete and the APS is in its final location — a remote endpoint of the zone for preference, a low point only where no reasonable remote location exists, and in either case somewhere water will not collect.
- Access to the APS ball valve. It does not need to be open when you arrive — you open it at step 2, after the dial is closed.
- The model and the zone volume. Read the model — APS2 or APS4 — and know the volume in gallons of the zone this APS serves. Both determine the setting where no manifold is installed. Where a PowerSaver manifold is installed the setting is fixed instead — see below.
Tuning an APS with no manifold connected
This is the procedure for an APS with no manifold connected. If a PowerSaver manifold is connected, use the procedure further down instead — it starts differently and it interrupts purity reporting.
| Step | What you should see |
|---|---|
| 1. Turn the flow dial fully closed, clockwise. | Every tuning starts from closed — setting the dial by feel from wherever it happens to sit does not give a repeatable flow. |
| 2. Bring the zone to supervisory pressure, then open the APS ball valve slowly. | Pressure comes up to the APS under control and the bead lifts off its seat. Opening a ball valve fast on a pressurized line drives the bead hard and vents at your face. |
| 3. Look up the setting for this zone — the label on the back of the APS, or the table below. | A letter, or a letter with a fraction: 1/4, 1/2, 3/4, A, A+1/2, B, C, D, E and so on. The lettered marks run A at the bottom of the sight tube to E at the top, with graduations between them. Match the setting to the marks on the unit in front of you; if you cannot identify the mark the setting names, call South-Tek Tech Support rather than estimating it. |
| 4. Slowly open the dial counter-clockwise until the center of the float bead reaches that setting. | The bead rises as you open. Read the center of the bead against the scale, not its top or bottom edge — the difference is most of a quarter step. If the bead does not lift at all as you open the dial, stop and go to troubleshooting; do not keep opening it. |
| 5. Let the bead stabilize, then read it again. | It settles and holds. If it drifts or hunts, it has not stabilized — wait before adjusting further. |
Flow settings by zone volume
These tables apply to an APS with no manifold connected. The setting is determined by the APS model and the volume of the zone it serves. Where a PowerSaver manifold is installed, ignore them — the setting is fixed, and the next section gives it.
APS2 — zones to 1,050 gallons
| Zone (gallons) | Flow setpoint | Zone (gallons) | Flow setpoint |
|---|---|---|---|
| 50 | 1/4 | 600 | C |
| 100 | 1/2 | 650 | C+1/4 |
| 150 | 3/4 | 750 | C+1/2 |
| 200 | A | 800 | C+3/4 |
| 250 | A+1/2 | 850 | D |
| 300 | A+3/4 | 900 | D+1/4 |
| 350 | B | 950 | D+1/2 |
| 400 | B+1/4 | 1,000 | D+3/4 |
| 500 | B+1/2 | 1,050 | E |
| 550 | B+3/4 |
APS4 — zones from 1,100 to 4,000 gallons
| Zone (gallons) | Flow setpoint | Zone (gallons) | Flow setpoint |
|---|---|---|---|
| 1,100–1,200 | A | 2,600–2,750 | B+3/4 |
| 1,250–1,500 | A+1/4 | 2,800–3,050 | C |
| 1,550–1,700 | A+1/2 | 3,100–3,300 | C+1/4 |
| 1,750–1,900 | A+3/4 | 3,350–3,600 | C+1/2 |
| 1,950–2,050 | B | 3,650–3,850 | C+3/4 |
| 2,100–2,300 | B+1/4 | 3,900–4,000 | D |
| 2,350–2,550 | B+1/2 |
A zone volume that falls between two rows takes the setting for the next size up. A zone whose volume you do not know has to be calculated from the pipe schedule before tuning — do not estimate it from the dial.
Tuning an APS with a PowerSaver manifold connected
Where a Quick-Check PowerSaver manifold is connected to the APS, the zone-volume tables do not apply. The manifold gates purging on measured purity, so the APS is set to one fixed flow.
| Step | What you should see |
|---|---|
| 1. Confirm the zone is at supervisory pressure and the APS ball valve is open. Notifications made. | Same prerequisites as any tuning. A bead set on a zone still coming up to pressure will not hold. |
| 2. If you are opening more than one zone this visit, mark each 1/4 in. line to its APS. Then remove the 1/4 in. OD tubing from the APS adapter and secure the free end. | The line is open and discharging. Do not leave a pressurized line loose and keep your face clear of the open port. A line reconnected to the wrong zone reports the wrong zone's purity and nothing downstream will catch it. |
| 3. Turn the flow dial fully closed, clockwise. | The bead settles to the bottom. |
| 4. Slowly open counter-clockwise until the center of the bead reaches D, and let it stabilize. | The bead rises to D and holds. Same reading rule as before — the center of the bead, not an edge. |
| 5. Reconnect the 1/4 in. tubing to the APS adapter. | The bead usually drops once the tubing is back on. A partial drop is expected and is how the manifold works — do not re-open the dial to bring it back to D, which over-purges the zone. If the bead falls to the seat and stays there there is no flow; treat that as the no-float fault in troubleshooting, not as normal. |
| 6. Restore reporting and confirm it. | Every line secure and on its own APS. Alarms do not clear by themselves — reset the flow alarm at the manifold — Menu, then Alarm Info, then the Reset Alarm block; a reset code is required, from the site's system documentation or South-Tek Tech Support — and confirm the alarm status reads inactive. Zone status updates on the manifold's sampling schedule, not immediately, so confirm the zone reads again at its next sample rather than waiting at the panel; do not change the sampling settings to force one. Where a monitoring company was told, confirm the trouble signal cleared at their end. |
Verifying the final setting
Before you leave the zone:
- The APS ball valve is open. A zone whose APS valve is shut does not purge at all.
- The float bead is stable at the setting you left it on.
- If a manifold is installed: the 1/4 in. tubing is reconnected and secure at both ends, and on its own APS. A loose sample line reads as no flow.
- If a manifold is installed: the flow alarm has been reset and reads inactive, and where a monitoring company was told, the trouble signal cleared at their end.
And after the visit: zone status updates on the manifold's sampling schedule — once daily by factory default — so the zone will not report again while you are still on site. Confirm at the next scheduled sample that it reports and the flow alarm has not re-triggered, and record on the ticket who is going to check it.
- Record the setting — the zone, the APS model, the volume used and the setting left on the dial. The next technician has no way to tell a tuned APS from an untuned one by looking at it.
Why the setting matters
- Too little flow and the zone never reaches its purity setpoint, so the purity alarm stays up and the corrosion protection the nitrogen is there to provide is not being delivered.
- Too much flow and the zone vents nitrogen it does not need, running the generator and the compressor continuously to replace it.
- A setting other than the specified one can also stop the alarms working as intended, which is the failure that does not announce itself. Set it to the specified value rather than to whatever quiets a symptom.
Troubleshooting
| What you see | What it means and what to do |
|---|---|
| The black ball does not float in the chamber at all, at any dial position. | There is no flow through the APS. Opening the dial further fixes neither cause and leaves the zone set wrong once flow returns. Work through them in order: use the bleed screw to relieve the water check; if flow does not return, the wye strainer needs cleaning — close the APS ball valve first, clean the strainer, then reopen the valve slowly and tune again from the start. While the valve is shut the zone is not purging. Leave the ball valve open once you are done unless the APS has taken water or is leaking; if it has to be left shut, note it on the report and tell the site contact, because that zone does not purge until it is reopened. |
| The bead floats but will not hold a setting — it drifts or hunts. | Confirm the zone is actually at supervisory pressure and has stopped filling. A zone still coming up to pressure will not give a steady reading. Give it time to settle before adjusting again. |
| The zone is tuned correctly but still reads out of specification. | Usually time rather than tuning — a zone drives its trapped air out over an extended period. Confirm the volume you tuned to is the real zone volume, then let it purge. Do not open the dial past the specified setting to speed it up. |
| The flow alarm re-triggers after you reset it. | The zone still has no sample flow. Check the tubing is seated at both ends and on the right APS, and that the ball valve is open. Until it clears, this manifold is not reporting purity or flow on any of its zones — keep the site contact and the monitoring company informed and call South-Tek Tech Support. Do not disable the alarm. |