The APS is a calibrated purge point that continuously bleeds oxygen-rich trapped air out of a zone so nitrogen can replace it. It is fully pneumatic and needs no electrical power, which is why it can go where there is nothing to plug into.
One APS serves one zone, and where it sits determines whether it works. This article covers getting it in the right place and piped correctly. Setting its flow is a separate job — see APS Field Tuning Instructions.
What the assembly looks like
The APS ties into the sprinkler piping at the inspector's test connection. Working outward from the fire protection pipe, the assembly is built in this order. The drawing below shows all three arrangements — horizontal, the assembly on its own, and vertical.
| Order | Component | Notes |
|---|---|---|
| 1 | 1 in. NPT F x 1/2 in. NPT F reducing tee | Ties into the existing 1 in. line at the inspector's valve. Not used on a vertical pipe — see below. |
| 2 | Elbow | Turns the assembly off the tee. Not used on a vertical pipe either. The drawing does not dimension it — the only elbows it sizes are the existing 1 in. elbows on the inspector's test line, which are different parts. |
| 3 | 1/2 in. NPT ball valve | The isolation valve. Normal operating position is open. This is the valve you close for water work. |
| 4 | 1/2 in. NPT wye strainer | The only recurring maintenance item on the assembly. Cleaned quarterly. Install it with the screen leg pointing down, as the drawing shows — inverted it will not hold what it catches. |
| 5 | APS body | Joins the strainer on a plain right hand thread. Carries the sight tube, the flow meter adjustment knob — the drawing's name for what this article calls the flow dial — and the output adapter port. |
The tie-in point is the zone's existing 1 in. inspector's test line. The drawing marks the 1 in. elbows, the 1 in. inspector's valve and the 1 in. pipe to drain as existing — those stay where they are. Only the four fittings in rows 1 to 4, and the APS body itself, are added.
Two things go on the assembly and are easy to leave off. An equipment identification tag hangs on the APS so anyone tracing the system can identify it, and the label on the back of the APS carries that model's flow settings — do not paint over it, cover it or mount the unit with the label against a wall. It is the only setting reference at the device.
Where the APS goes
Two things decide the location, and they pull in the same direction. The drawing makes the first a requirement and the second a recommendation — treat them that way.
- Where water will not collect — this one is a requirement. The drawing's installation note reads mount APS at a point in which water will not collect within the fire protection piping. Water reaching an APS on a pressurized system puts it out of service: it has to be stripped, drained, cleaned and dried, the strainer cleaned, the tubing cleared and the flow retuned before that zone works again.
- As far from the pump room as possible. The drawing recommends rather than requires this one, in those words: we recommend to place the APS as far from the pump room as possible. What you are after is a remote endpoint of the zone — that is the air the generator cannot otherwise reach. A purge point near the riser sweeps the piping you were least worried about.
A low point is an option only where no reasonable remote location exists, and it is not preferred. That is South-Tek's position, not the drawing's — the drawing sanctions no low point at any level. Where you have to use one, the water requirement above still governs, so satisfy that first and treat the low point as the compromise it is.
It also has to be somewhere a technician can actually get to. The APS is tuned at commissioning, read during service visits and cleaned quarterly, so a location that needs a lift or a ceiling tile pulled every time will quietly stop being maintained.
Horizontal and vertical pipe
Both are covered by the installation drawing. The ball valve, the wye strainer and the APS are identical either way — same parts, same order working outward from the pipe. Only how the assembly reaches the pipe changes.
| Pipe run | How it connects | What changes |
|---|---|---|
| Horizontal | Through the 1 in. NPT F x 1/2 in. NPT F reducing tee and elbow at the inspector's test connection. | Nothing. This is the standard arrangement described above. |
| Vertical | Through an FPS coupling with a 1/2 in. FNPT connection into the vertical pipe. | Remove the reducing tee and the elbow. The drawing boxes both and labels the box customer to remove these parts when installing on a vertical section of pipe. Everything downstream — ball valve, wye strainer, APS — is unchanged. |
The output adapter port
One port on the APS body does three different jobs, which is the source of most confusion about it:
- Spot checks by hand. A Quick-Check Portable Nitrogen Purity Sensor, part number A02-QCP, connects here to read that zone. Regulate the sample: the handheld operates between atmospheric pressure and 3 psig and takes no more than 2 litres per minute. Over-pressurizing may destroy the sensor and void its warranty.
- Continuous monitoring. 1/4 in. OD poly tubing runs from this port back to that zone's port on a Quick-Check PowerSaver manifold, through an APS adapter, part number A03-MA. Those adapters ship with the 6, 10 and 20 port PowerSaver manifolds — one per zone — so on a manifold job they are already on site and do not need ordering separately. Where no manifold is installed, no tubing is present.
- Draining to a floor drain. In water sensitive areas the APS can be plumbed from this port to a drain using the N2-Blast APS Water Drain Adapter Kit, part number A03-WDK. That is a location-specific option, not part of a standard install — it does not replace siting the APS where water will not collect in the first place.
Spot checks and continuous monitoring are not exclusive: on a manifold system the tubing comes off this adapter for a spot check or for tuning and goes back on afterwards.
If a manifold is going in, run the tubing during installation and label both ends. A line landed on the wrong manifold port makes the system report the wrong zone's purity and reads perfectly healthy doing it.
Before water enters the piping
Close the ball valve at every APS before water is introduced into the sprinkler piping — hydrostatic testing, pressure testing, flushing, trip tests, or any pipe work that will wet the system. Two reasons:
- Water reaching an APS puts it out of service and it has to be stripped and cleaned.
- An APS left open during a pressure test bleeds a slow purge and distorts the test result.
The APS does carry a ball check valve that closes when a rush of pressure or water hits it. Treat that as a backstop, not a substitute — close the ball valve.
This is not a field convention. The installation drawing labels the ball valve close valve during hydrostatic testing, and the label on the back of the APS carries the same instruction: AutoPurge Systems should be valved off during all FPS pressure tests.
That water work is a fire protection impairment in its own right and is carried out under the site's impairment program; isolating the APS is a step inside it, not a substitute for it. Closing an APS also stops that zone's sample flow, which raises the flow alarm and trips the manifold's dry contact — and one contact serves the whole manifold, so while any APS is shut a genuine fault on another zone raises no new signal off site. Tell the site contact and the alarm monitoring company before you close anything.
Before you hand it over for tuning
Installation is finished when every one of these is true. The APS is not in service until it has been tuned.
- One APS per zone, each at a remote point of its own zone and reachable without special access. Horizontal or vertical, piped as the installation drawing shows for that orientation.
- Nothing can put water into it when the system is pressurized. Where the location is water sensitive, the A03-WDK drain kit is fitted or has been ruled out with South-Tek.
- Reducing tee and elbow, or an FPS coupling on a vertical run, then ball valve, wye strainer and APS body in that order, joints tight, strainer screen down. Any fitting in the output adapter port is made up on its left hand thread. The valve is closed for the nitrogen fill and leak check, and is opened at tuning — not before.
- Any 1/4 in. tubing is run through its A03-MA adapter, secure at both ends and labeled to the manifold port it belongs to.
- Where no manifold is fitted, each zone's volume in gallons is recorded — the flow setting is chosen from it, and it is far easier to establish now than later. With a manifold the setting does not depend on volume.
Keeping it working
Recurring APS maintenance is the strainer: clean it quarterly. Anything that restricts the sample path shows at the manifold as low or no flow, not as a strainer fault, so the strainer is worth checking before anything else is suspected.
Check two things at the same visit while you are at the unit: that the equipment identification tag is still on the assembly and legible, and that the settings label on the back of the APS has not been painted over or obscured. Both go missing quietly and both are needed by whoever comes next.