This article provides the official South-Tek installation and startup checklist for N2-BLAST® FPS nitrogen generators. It is intended for licensed fire protection contractors performing new system commissioning. Completion and submission of this checklist is required to activate the South-Tek limited warranty.
Download the Checklist
The checklist is a fillable PDF covering all FPS models. Print it, complete it on site, and submit the finished copy to South-Tek to activate your warranty.
📄 FPS Installation & Startup Checklist — Rev 4
Covers all FPS models · Rev 4 · PDF · 2 pages
What the Checklist Covers
The checklist walks through every required commissioning step in sequence. Below is a section-by-section summary.
| Section | What It Verifies |
|---|---|
| 1–2. System Purpose & Checklist Scope | N2 generator function, corrosion inhibition, and commissioning objectives |
| 3. Safety Requirements | Lockout/tagout, PPE, pressure isolation, ventilation, model-specific temperature limits |
| 4–5. Site & System Identification | Facility, installer, model, and serial number documentation |
| 6. Electrical Verification | Nameplate voltage, measured voltage, dedicated circuit, disconnect |
| 7. Compressor Verification | Shipping bolt removal (integral models), external compressor confirmation, dryer status, rotation check |
| 8. Mechanical Installation | Mounting, clearances, drain lines, relief valves, bypass piping; forklift requirements for FPS-10000/16500/22500 |
| 9. Pressure Setup | Standby (cut-out) pressure recorded by model family; air inlet regulator verified at 120–125 PSIG static |
| 10. Dryer Verification | Dryer powered, alarms clear, auto drains connected (FPS-3250/5000/10000/16500/22500) |
| 11. FPS Leak Testing | NFPA acceptance limits: ≤1.5 PSI/24 hrs (new) or ≤3 PSI/2 hrs (existing); pass/fail documented |
| 12. AutoPurge Setup | APS placement, height, flow setting, supervisory pressure, purge confirmation; Quick-Check setting D |
| 13. Purity Monitoring | Sample tubing, flow confirmation, facility demonstration of monitor and alarm interpretation |
| 14. Compressor Performance | Largest zone fills to supervisory pressure within 30 minutes per NFPA |
| 15. Alarm & BMS Verification | Common alarm relay test; BlastOff® simulation (procedure varies by controller); bypass alarm; Ethernet/Modbus |
| 16. Filter Maintenance Awareness | Replacement interval (1,000 hrs or 1 year), facility notification, model-specific alarm reset procedure |
| 17. Final Commissioning | System at standby, no alarms, purity confirmed, AutoPurge active, area clear, facility handoff complete |
| 18. Common Startup Issues | Quick-reference troubleshooting table for rapid cycling, BlastOff® alarms, AutoPurge issues, low purity, and more |
| 19. Contractor Certification | Installer signature, company, date — required for warranty activation |
Model-Specific Notes
The checklist is a single document that covers all FPS models. Sections that apply to only certain models are clearly labeled inline. Key model-specific items to be aware of:
- The FPS-500 and FPS-900 are wall-mounted with an integral compressor. Shipping bolts must be removed before startup.
- The FPS-1650 is floor-standing with an integral compressor and no external dryer requirement.
- The FPS-3250 and FPS-5000 require an external compressor and include an integrated air dryer.
- The FPS-10000, FPS-16500, and FPS-22500 require an external compressor, include an integrated air dryer, and require forklift equipment for unloading. Maximum ambient temperature is 90°F (vs. 100°F for all other models).
- The BlastOff® alarm simulation procedure differs between the 7-segment PLC display (FPS-500/900) and the SMART-Trak® touchscreen (all larger models) — both procedures are detailed in Section 15.
- The filter alarm reset procedure also differs by controller type — refer to Section 16.
Contact South-Tek Systems
Phone: (910) 415-1880
Email / Ticket: support@southteksystems911.zendesk.com