BlastOff® is South-Tek's leak detection and early warning set. It comes in four versions — so the first question on any BlastOff alarm is which one tripped.
| Version | What it watches | FPS-500 / 900 / 900-RS | FPS-1650 and larger |
|---|---|---|---|
|
BlastOff I leak detection |
Run time without reaching standby | Standard | Standard |
|
BlastOff II auto air bypass |
Air instead of nitrogen in the riser | Manual bypass valve; pooled onto the common alarm contact | Standard, on its own bypass alarm contact |
|
BlastOff III early warning system |
Equipment conditions | Option | Standard |
|
BlastOff IV onboard purity analyzer |
Nitrogen purity | Not available | Option |
If you are not sure what is fitted, check the order documents or ask Service with the serial number.
What BlastOff usually means
Usually one of these:
- There is a leak somewhere in the fire protection system
- The nitrogen demand is higher than the generator can supply
- The generator cannot build or hold pressure as expected
- The system has been bypassed by compressed air
- An equipment issue is affecting normal nitrogen generation
- Nitrogen purity has fallen below its alarm point, on units with purity monitoring fitted
BlastOff I — leak detection
BlastOff I watches for a generator that keeps running without ever reaching standby.
On the FPS-500, FPS-900 and FPS-900-RS the display flashes BLAsstoff 9H.Run. On the FPS-1650 and larger the BlastOff timer is a setting with a live countdown — read the timer on the unit rather than assuming a figure.
BlastOff II — auto air bypass
On the FPS-1650 and larger, bypass switches the riser to compressed air automatically when nitrogen cannot hold supervisory pressure. On the FPS-500, FPS-900 and FPS-900-RS it is a manual 3-way valve.
Either way the riser stays supervised but corrosion protection has stopped, so a bypass alarm is a live condition to resolve rather than a state to leave the system in. Bypass during a 30-minute fill test is expected; at any other time it means the generator is not keeping up.
BlastOff III — early warning system
The early warning system flags equipment conditions before they become failures, and points at the part of the system involved.
BlastOff IV — onboard purity analyzer
BlastOff IV reads nitrogen purity continuously and alarms when it falls below its alarm point. It requires the oxygen sensor, an option on every model.
The alarm point is a setting, not a fixed number, so check what yours is set to before treating a reading as a fault. Every current generator is specified to 98.5% nitrogen or better, which is the production spec and not the alarm point. Without BlastOff IV, purity is checked with a handheld analyzer instead.
What to check first
- Confirm which BlastOff version tripped.
- Check whether the unit is cycling normally or has been running continuously without reaching standby.
- Inspect the fire protection system for obvious leaks at fittings, couplings, and connection points.
- Review any relevant runtime, leakage, bypass, or purity logs if available.
How to isolate a possible leak
Listen, and spray soapy water around fittings and connections. If nothing shows, isolate the generator from the riser and see whether it reaches standby on its own.
- Shut the right valves. On the FPS-10000, FPS-16500 and FPS-22500, close the nitrogen outlet ball valve — there are two ½" ball valves inside, so read the label rather than working it out by position. On every other model, close both ball valves at the nitrogen storage tank. On the FPS-500, FPS-900 and FPS-900-RS the outlet is a 3-way valve, and turning it the wrong way puts the riser on air instead of isolating it.
- Note the storage tank pressure, leave the unit running, and give it 10 minutes to reach standby. Then wait 5 more minutes.
- Still in standby after those 5 minutes — the loss is past the generator. Where you closed the tank valves, read the storage tank gauge: if it has moved, the loss is at the tank fittings; if it has not, the loss is out in the building piping.
- Back to running, or never reaching standby at all — the loss is inside the cabinet. On the FPS-10000 and larger that includes the nitrogen storage tank, which the closed outlet valve leaves connected.
What to check for bypass-related alarms
- Confirm whether the system is intentionally or unintentionally in air bypass mode.
- Review bypass history if the system supports logging.
- Return the system to normal nitrogen supervision if the bypass is no longer required.
What to check for purity-related alarms
- Confirm the unit has BlastOff IV fitted.
- Review recent purity trend data if available.
- Check the alarm point the controller is set to. A purity dip while recovering from a large draw is not the same as a failing unit.
When to contact support
Contact support if:
- The system will not reach standby
- You cannot identify the source of the leak or abnormal demand
- BlastOff alarms return after the cause has been fixed and the alarm reset
- The system repeatedly enters air bypass unexpectedly
- Purity alarms continue after the system has had time to stabilize
Related articles
- BlastOff and SMART-Trak Overview for N2-BLAST Systems
- FPS-500 and FPS-900 Operation, Alarms, and Maintenance
- FPS-1650, FPS-3250, and FPS-5000 Operation, Alarms, and Maintenance
- FPS-10000, FPS-16500, and FPS-22500 Operation and Alarms