Applies to: STS Series (5–30HP) · STSH Series · STSD · STSP · STSP2
Before Every Start
⚠ Warning Never operate the compressor if any mechanical, hydraulic, or electrical component is known to be defective. Resolve all faults before starting.
- Check oil level at the sight glass. Oil must be at or near the upper limit. Do not start if oil is at or below the minimum mark.
- Confirm all cabinet doors are closed and latched.
- Verify the AirMASTER FORM controller shows no active faults.
- Confirm the air outlet valve is open.
Starting the Compressor
- Open the air outlet valve.
- Energize the compressor at the main disconnect.
- Press the START button on the AirMASTER FORM controller panel.
- The compressor will start and begin loading after the configured delay time expires.
ℹ Note The control air operating pressure at the suction control valve is preset to 6 bar (87 psi) and must not be adjusted. Verify this setting while the compressor is running.
During Operation
During normal operation the compressor cycles automatically between load and unload states based on system pressure:
- Load: The compressor is compressing air and supplying the system. The suction control valve is open.
- Unload: System pressure has reached the upper setpoint. The suction control valve closes and the compressor runs unloaded. If system pressure does not drop to the lower setpoint within the idle timer period, the compressor stops automatically.
- Auto-restart: When pressure drops to the lower setpoint, the compressor restarts automatically and returns to load.
⚠ Warning — Automatic Operation If the automatic restart parameter is enabled, the compressor will restart without operator input after a power interruption. Confirm this parameter's state before performing any maintenance. It is disabled in default factory settings.
Routine Checks During Operation
- Monitor the AirMASTER FORM display regularly for temperature, pressure, maintenance reminders, and fault alerts.
- Periodically verify the scavenge line check valve has oil flowing — this confirms the scavenge line is functioning.
- Keep all cabinet doors closed at all times during operation. Never touch internal components or piping while the unit is running.
Checking Oil Level During a Run
- Press the STOP button and wait for the compressor to fully stop.
- Wait a few minutes for oil to settle.
- Check the sight glass — oil should be at or near the upper limit.
- If oil is low, press Emergency Stop, close the outlet valve, discharge all compressed air from the system, then add oil per the oil filling procedure.
- Always investigate the cause of oil loss before returning the unit to service.
Stopping the Compressor
ℹ Note Under normal conditions, always stop using the STOP button — never the Emergency Stop button.
- Press the STOP button on the control panel.
- The compressor will run unloaded for the configured unload time, then stop.
- Close the air outlet valve.
- Discharge pressure in the pipes between the air tank and the outlet valve using the manual drain valve or by pressing the test button on automatic drain valves.
Emergency Stop
In an emergency, press the Emergency Stop button to stop the compressor immediately. This creates an emergency stop fault condition. To recover:
- Resolve the condition that required the emergency stop.
- Unlock the Emergency Stop button by rotating it.
- Press and hold the Escape button on the AirMASTER FORM to reset the fault.
- Restart normally.
Fault Recovery
If a fault causes the compressor to stop during operation, the fault information is displayed on the AirMASTER FORM controller screen. Resolve the underlying issue, reset the fault on the controller, then restart the compressor and monitor its operation.
Related Articles
- AirMASTER FORM Controller - Overview & Navigation
- Troubleshooting Guide
- First Start-Up & Commissioning Checklist
For fault code reference, see the Troubleshooting Guide article or contact South-Tek Systems: (910) 415-1880 or support@southteksystems911.zendesk.com